Chapter 4. WIRING

4-5 Power Supply and Grounding

Power supply

Instrument power supply
100 to 240V AC
50/60Hz
Other circuits
HANDLING PRECAUTIONS

Grounding

HANDLING PRECAUTIONS
4-6
To supply power to the DCP551, use an instrument-dedicated single-phase power sup-
ply subject to minimal electrical interference.
200 to 240/200 to 240V
110 to 120/110 to 120V
Insulating transformer
• If electrical interference proves excessive, we recommend adding an insulat-
ing transformer and/or using a line filter.
model No.: 81446364-001
• After carrying out interference reducing measures, do not bundle the primary
and secondary power supply coils together or insert them in the same conduit
or duct.
If grounding the shield wire or other lines proves difficult, ground them separately to a
grounding terminal block.
Type
: Less than 100Ω
Conductor
: Annealed copper wire, min. 2mm
Max. Length
: 20m
Grounding terminal block
Less than 100
To ground the DCP551, connect the FG terminal (terminal (52) or (53) to a sin-
gle ground point without jumpering.
Recommended product
81446364-001
Line filter
1
3
GND
E
2
4
Grounding
2
,+2##
or
52
FG terminals
Shield
DCP551
39
40
or
53
52
Grounding
(AWG14)
53