Honeywell DCP551 Mark ΙΙ User Manual page 27

Digital control programmer
Table of Contents

Advertisement

●DC current, DC voltage
Input type
Symbol
Code
Range No.
C01
mA
Z51
(Linear)
M01
mV
L02
C01
mA
Z51
(Linear)
V
(Linear)
V01
HANDLING PRECAUTIONS
Input range (FS)
48
4 to 20mA
52
2.4 to 20mA
49
0 to 10mV
50
-10 to +10mV
51
0 to 100mV
128
4 to 20mA
134
2.4 to 20mA
129
0 to 1V
130
-1 to +1V
131
1 to 5V
132
0 to 5V
133
0 to 10V
• The unit for code Z06 is "K" (kelvin).
• Code F50 and P50 do not generate the PV lower bound alarm.
• The number of decimal digits for DC current and DC voltage is programmable
from 0 to 4.
• The lower limit readout of code B18 is 20°C (68°F).
Chapter 2. NAMES AND FUNCTIONS OF PARTS
Accuracy (under standard conditions)
±0.1%FS
Programmable range
–19999 to +20000
±0.1%FS
(Decimal point
±0.1%FS
position is variable.)
±0.1%FS
±0.1%FS
±0.1%FS
±0.1%FS
±0.1%FS
±0.1%FS
±0.1%FS
±0.1%FS
±0.1%FS
2-9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dcp550