Chapter 7. PARAMETER SETUP
No.
Item code
PV channel switching dead
28
C 28
band
29
Selections available when
C 29
power is on during PV
channel switching
PV equalizer
30
C 30
31
End of operation
C 31
Manipulated variable in READY mode
32
C 32
33
Manipulated variable setting
C 33
in PV overrange
Manipulated variable in PV
34
C 34
overrange
Manual change mode
35
C 35
Preset MANUAL value
36
C 36
Unused
37
C 37
Unused
38
C 38
39
Unused
C 39
Unused
40
C 40
41
Unused
C 41
42
Unused
C 42
Length of outage permitting
43
C 43
continuous operation
44
Unused
C 44
Auxiliary output 1 type
45
C 45
46
Auxiliary output 1 lower limit
C 46
(4mA)
Auxiliary output 1 upper limit
47
C 47
(20mA)
7-24
Factory default
Item
settings
100 PVU
0
0
0
0.0
0
0.0
0
0.0
----
----
----
----
----
----
0
----
0
0 SPU
10000SPU
User
Settings and descriptions
settings
1 to 1000 PVU (PV1)
[Description:]
Ò-----Ó is displayed and setting cannot be performed on
model with one PV input channel.
When
is set to more than 1, Ò-----Ó is displayed and
C25
setting cannot be performed.
When
is set 0, Ò-----Ó is displayed and setting cannot be
C26
performed.
0: Continues until power is turned off
1: PV1
2: PV2
3: High-temperature PV
4: Low-emperature PV
[Description:]
Ò-----Ó is displayed and setting cannot be performed on
model with one PV input channel.
When
is set to more than 1, Ò-----Ó is displayed and
C25
setting cannot be performed.
When
is set 0, Ò-----Ó is displayed and setting cannot be
C26
performed.
0: No
1: PV1 only
2: PV2 only
3: PV1 and PV2
[Description:]
The range of settings is 0 to 1 on model with one PV
input channel.
0: READY mode
1: END mode
Ð5.0 to +105.0 %
0: No
1: Yes
Ð5.0 to +105.0 %
0: smooth
1: preset
[Description:]
When
is set to 0, the output is smooth regardless of
C21
setting.
Ð5.0 to +105.0 %
[Description:]
Ò-----Ó is displayed and setting cannot be performed.
0 to 3600sec
When set to 0, operation continues regardless of outage time.
[Description:]
The HOLD mode is invoked when the outage is longer than set time.
The measurement of a power outage may vary by about 10 seconds.
[Description:]
Ò-----Ó is displayed and setting cannot be performed.
0: SP
1: PV
2: Deviation (DEV)
3: Manipulated variable (MV)
4: PV1
5: PV2
[Description:]
Ò-----Ó is displayed and setting cannot be performed on
model without auxiliary output.
Ð19999 to +20000 SPU (
Ð1999.9 to +2000.0 SPU (
[Description:]
Ò-----Ó is displayed and setting cannot be performed on
model without auxiliary output.
not equal to 3)
C45
set to 3)
C45