Current output calibration

Scroll ↑, ↓, ←, or → keys to show (
ENTER key.
Connect the digital ammeter across terminals (See Figure 12-9).
OUT CH1 output calibration
(1) Press SETUP key until the PROG/SEG display shows (
(2) Press SETUP key until the PROG/SEG display shows (
OUT CH2 output calibration
(1) Press SETUP key until the PROG/SEG display shows (
(2) Press SETUP key until the PROG/SEG display shows (
AUX CH1 output calibration
(1) Press SETUP key until the PROG/SEG display shows (
(2) Press SETUP key until the PROG/SEG display shows (
AUX CH2 output calibration
(1) Press SETUP key until the PROG/SEG display shows (
(2) Press SETUP key until the PROG/SEG display shows (
Scroll ↑, ↓, ←, or → keys until meter indicates 4.00mA, then press ENTER key.
Scroll ↑, ↓, ←, or → keys until meter indicates 20.00mA, then press ENTER key.
Scroll ↑, ↓, ←, or → keys until meter indicates 4.00mA, then press ENTER key.
Scroll ↑, ↓, ←, or → keys until meter indicates 20.00mA, then press ENTER key.
Scroll ↑, ↓, ←, or → keys until meter indicates 4.00mA, then press ENTER key.
Scroll ↑, ↓, ←, or → keys until meter indicates 20.00mA, then press ENTER key.
Scroll ↑, ↓, ←, or → keys until meter indicates 4.00mA, then press ENTER key.
Scroll ↑, ↓, ←, or → keys until meter indicates 20.00mA, then press ENTER key.
Chapter 12. CALIBRATION
6.0.6.6.
) on the upper display, then press
06-01
06-02
06-03
06-04
06-05
06-06
06-07
06-08
).
).
).
).
).
).
).
).
12-15