Honeywell DCP551 Mark ΙΙ User Manual page 61

Digital control programmer
Table of Contents

Advertisement

Chapter 5. FUNCTIONS
Code event
Example: Setting a code event involving 3 output points in event 3
Segment
Set value
Code value
1 in event 3
Code value
2 in event 4
Code value
4 in event 5
Output code
5-12
Several events are used as one group and the number of output points are output as one
parallel code number. Assigning code numbers to event outputs has the same effect as
increasing the number of physical output points.
• Code event
Set event type to code event and set the number of output points (1 to 8) in auxiliary
setting 1. An output code value (0 to 255) can be set for each segment. A binary
coded low-order bit for the set number of output points is output.
The previous setting is valid until the program reaches a segment with a new setting.
Note, however, that unless a setting is made in the first segment, the program will
assume that a set value of 0 is set in the first segment.
The table below shows the output state when a value of 3 is set in segment 2, a value of 6 is
set in segment 4 and a value of 0 is set in segment 5.
1
2
Not set
3
ON
OFF
ON
OFF
OFF
OFF
3
0
OFF,ON,ON
OFF,OFF,OFF
0, 1, 1
0, 0, 0
3
4
Not set
6
ON
OFF
ON
ON
ON
OFF
3
6
OFF,ON,ON
ON,ON,OFF
0, 1, 1
1, 1, 0
5
0
OFF
OFF
OFF
0
OFF,OFF,OFF
0 , 0, 0