Chapter 7. PARAMETER SETUP

Constant value control data setting

No.
Item code
1
Control mode
ConSt
2
Setpoint
SP
Proportional band
3
P
4
Integral time
I
5
Derivative time
d
Manual reset
6
rE
Manipulated variable lower limit
7
oL
8
Manipulated variable upper limit
oH
7-34
Factory default
Item
settings
0
0
100.0
0
0
50.0
0.0
100.0
User
Settings and descriptions
settings
0: Program run mode
1: Constant value control mode
[Description:]
When setup
is set to 0, this setting is automatically
C21
set to 0.
Within the range of setup
0.0 to 1000.0%
A setting of 0.0 turns on ON-OFF control
0 to 3600sec
No integral operation when set to 0.
[Description:]
When
is set to 0.0, Ò-----Ó is displayed and setting cannot be performed.
P
0 to 1200 sec
No integral operation when set to 0.
[Description:]
When
is set to 0.0, Ò-----Ó is displayed and setting cannot be performed.
P
0.0 to 100.0%
[Description:]
When
is set to 0.0, Ò-----Ó is displayed and setting cannot be
P
performed.When I is not equal to 0, Ò-----Ó is displayed and
setting cannot be performed.
Ð5.0% to upper limit
Lower limit to +105%
to
(SP limit)
C66
C67