Setting Repeat Items - Honeywell DCP551 Mark ΙΙ User Manual

Digital control programmer
Table of Contents

Advertisement

Setting repeat items

Display
NOTE
(1) In the set value display state, move to the repeat item to be set for the segment on the
programming map.
(2) Press the ENTER key to make display panel 1 flash (registration of first setting).
(3) Use the ↑, ↓, ←, and → keys to make the first setting – setting the number of the
return segment.
Setting range: 0 to segment number in setting
(4) Press the ENTER key to stop the flashing on display panel 1 and display panel 2
starts flashing. (Start of second setting)
Note, however, that when the first setting is 0, "-----" is shown in the second panel
which does not flash.
(Pressing the FUNC and CLR keys causes display panel 1 and 2 to return to unset
rP.0/
state "
-----" and the flashing stops.)
(5) Use the ↑, ↓, ←, and → keys to make the second setting (repeat segment times).
Setting range: 1 to 10000
(6) Press the ENTER key to stop the flashing on display panel 2.
(Pressing the FUNC and CLR keys causes display panel 1 and 2 to return to unset
rP.0/
state "
-----" and the flashing stops.)
Set number of return segment
Set repeat count value
R E P E A T S E G M E N T
T I M E S
• Unset values are indicated as "
C59
• When setup data
and not displayed.
When the number of return segment is something other than 0, it uses a subfunction.
A subfunction cannot be used when a setting has not been made "
PROG
Program
number
PROFILE
Pattern trend
rP.0/
-----".
is set to 1, a repeat item on the programming map is skipped
Chapter 8. PROGRAM SETUP
SEG
Segment
number
rP.0/
-----".
8-15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dcp550

Table of Contents