Chapter 8. PROGRAM SETUP

Setting PV shift items

Display
NOTE
HANDLING PRECAUTIONS
8-14
(1) In the set value display state, move to the PV shift item to be set for the segment on
the programming map.
(2) Press the ENTER key to make display panel 2 flash (registration of first setting).
(3) Use the ↑, ↓, ←, and → keys to make the first setting – setting the PV shift set
value.
Setting range: –10000 to +10000 SPU
(4) Press the ENTER key to stop the flashing on display panel 2.
(Pressing the FUNC and CLR keys causes display panel 1 to return to unset state
"-----" and the flashing stops.)
Set PV shift value
P V S H I F T
• Unset values are indicated as "-----".
C59
• When setup data
is set to 1, a PV shift item on the programming map is skipped
and not displayed.
PV shift uses a subfunction. A subfunction cannot be used when a setting has not been
made "-----".
• When PV shift is not set, it is a sequel to a PV shift value in a previous seg-
ment. When PV shift is not set in the first segment, the set value is 0.
PROG
SEG
Program
Segment
number
number
PROFILE