4-7 Control Output Connection

Be sure to turn off the power supply when you are installing or
removing the controller. Failure to heed this warning may lead to
electric shock.

Current output

Voltage output

HANDLING PRECAUTIONS

Open collector output

HANDLING PRECAUTIONS
WARNING
+
-
43
44
+
-
Load
+
-
43
44
+
-
SSR
The voltage output is a constant current circuit inside. The SSR used is set to an
optimum voltage to meet the requirements of hte load. Enter the value in the
setup data. A normal SSR voltage has been set at the factory before shipment.
43
44
+ -
12 to 24V DC
Load
• Do not short-circuit the positive (+) terminal of the external power supply to
terminal (43) on the DCP551. Doing so causes the open collector outputs to
malfunction. (There is no short circuit preventing circuit inside.)
• When connecting a semiconductor load such as a programmable controller
(sequencer), select a module in which the current directions match.
Use one made inoperative by the leakage current produced when the digital
outputs are shut off.
4 to 20mA DC
Load resistance less than 600
2 to 22mA DC
With current value adjustment function
(Setup data
)
C95
Max. load current : 100mA
Leakage current when off : less than 0.1mA