NOTE
• Guidelines for battery service life are given below.
When the DCP551 is stored with the power off under standard conditions (ambient
temperature 23±2°C): 5 years
When the DCP551 is stored with the power on under standard conditions (ambient
temperature 23±2°C): 10 years
Battery life is reduced when stored at higher temperatures.
• When the BAT LED is flashing, memory data is protected if the power is on.
• When the data in memory is corrupted, one of the following two conditions will
occur.
g.rESt
(1) "
(Press the ENTER key to perform a general reset and reset parameters to their
factory default values and delete all program settings.
(2) Normal operation can be started at power up but one of the alarm codes
AL97
are displayed.
" is displayed at power up and normal operation cannot be performed.
Chapter 10. TROUBLESHOOTING
AL93
to
10-11