Chapter 11. SPECIFICATIONS

11-1 Specifications

Item
No. of programs
Program
section
No. of segments
Segment setting system
Segment time
Segment slope
Segment
No. of sub-function
Sub-function function
Event (16 point)
PID group setting
Output limiter group
G.SOAK
PV shift
Repeat
PV start
Cycle
Pattern link
Tag
Basic time accuracy
Input type
Input section
Input sampling cycle
Input bias current
Input impedance
Measurement current
Influence of wiring
resistance
Resistance temperature
detector input
Allowable parallel resistance
Max. allowable input
Burn out
Range over assessment
Cold junction compensation accuracy
99 programs
99 segments/1 program, or total 2000 segments
RAMP-X: Setting by set points (SP) and time.
RAMP-T: Setting by set points (SP) and slope ( ).
RAMP-E: Setting by set points (SP) or
0 to 500 hours 00 min, 0 to 500 min 00sec, or 0.0 to 3000.0sec (Time unit is switchable.)
1 to 10000U/hours, 1 to 10000U/min, or 1 to 10000U/sec (Time unit is switchable.)
SP
1 to 10000U/1 pulse
4000 settings
Event, PID group, output limiter group, G.SOAK, PV shift, repeat
Operating point set as specified by event type.
Group 0 (continuing from previous segment), groups 1 to 9, group A (automatic
changeover) and ON-OFF control settable.
Group 0 (continuing from previous segment), groups 1 to 9 settable
Type (start point, end point, all) and G.SOAK width 0 to 1000U settable
-10000 to +10000 settable
Return segment number and repeat count settable.
Type settable for each program (ascending, descending and bi-directional)
Cycle count number settable for each program
Program numbers 0 to 99 (program 0 without link) settable for each program
8 characters consisting of alphanumerics, katakana and symbols settable for each program
–0.01% (segment time setting = 0, repeat; each cycle and repeat slows the process by 0.1sec)
Thermocouple
Resistance temperature detector (RTD)
DC current
DC voltage
Multi-range of thermocouple, Resistance temperature detector, DC voltage,
and DCcurrent(see page 2-8, 2-9)
0.1s
Thermocouple, DC voltage input: Max.
conditions). The range higher than 1V is Max. -3 A.
DC current input: approx. 50
RTD input: approx. 1mA, Current input on terminal A. (under operating conditions)
Thermocouple, DC voltage input:
Resistance temperature detector input:
The ranges except F01, F33, P01, and P33 are lower than 85 .
(Includes the zener barrier resistor value. However, spot adjustment is needed.)
The ranges of F01, F33, P01, and P33 are lower than 10 .
(Zener barrier cannot be used.)
Thermocouple disconnection detection allowable parallel resistance : Higher than 1M
Thermocouple, DC voltage input:-5 to +15Vdc
DC current input
Burnout on/off selectable
100% FS or more: upscaled
-10% FS or less : downscaled
0.5
(under standard conditions)
Specifications
SP per pulse of external switch input.
K,E,J,T,B,R,S (JIS C1602-1981)
WRe5-26 (Hoskins Data)
PR40-20 (Johnson Matthey Data)
N (N.B.S. Monograph 161)
PLII (Engelhard Industries Data (IPTS68))
Ni-NiMo (General Electric Data)
Gold iron chromel (Hayashidenko Data)
Pt100,JPt100 (JIS C1604-1989)
4 to 20mA, 2.4 to 20mA
0 to 10mV, -10 to +10mV, 0 to 100mV,
0 to 1V, -1 to +1V, 1 to 5V, 0 to 5V, 0 to 10V
1.3 A (peak value, under standard
(under operating conditions)
Thermocouple
DC voltage (lower than 1V range)
DC voltage (5V range)
DC voltage (10V range)
Max.
0.01% FS/ within wire resistor 0 to 10W
The ranges of F01, F33, P01, and P33 are Max. 0.02% FS/
: 50mAdc, 2.5Vdc
(However, inputs in the F50 range are not downscaled.)
: 0.5 V/
: 0.5 V/
: 3 V/
: 6 V/
.
11-1