Variable Parameter Setting - Honeywell DCP551 Mark ΙΙ User Manual

Digital control programmer
Table of Contents

Advertisement

■ Variable parameter setting

No.
Item code
PA 01
1
Keylock
2
PA 02
Memory protect
PA 03
3
Unused
PA 04
4
Unused
PA 05
5
Program auto load *
PA 06
6
Unused
PA 07
7
Unused
PA 08
8
Auto-tuning
PA 09
9
Auto-tuning MV lower limit
PA 10
10
Auto-tuning MV upper limit
PA 11
11
SP bias
PA 12
12
PV1 digital filter
PA 13
13
PV1 bias
PA 14
14
Manipulated variable deviation limit
PA 15
15
Time proportional output cycle
PA 16
16
On-off control differential
PA 17
17
PID computation initialize manipulated variable
PA 18
18
Unused
PA 19
19
Unused
PA 20
20
Unused
PA 21
21
Unused
PA 22
22
PV2 digital filter
PA 23
23
PV2 bias
* : This function is available on the DCP551E***** model only.
Factory default
Item
settings
0
0
0
0
0.0
100.0
0 SPU
0.0
0 PVU
110.0
10
50 SPU
0.0
-----
-----
-----
-----
0.0
0 PVU
Chapter 7. PARAMETER SETUP
User
Settings and descriptions
settings
0: Keylock disabled
1: Display of setup data settings disabled
2: Display of all settings disabled
3: Display of all settings disabled. Operation keys disabled
[Description:]
PA01
can be displayed and changed regardless of
settings.
0: Disabled
1: Program settings are protected
2: Setup, variable parameters and event configurations
are protected.
3: Setup, variable parameters and event configurations
are protected.
4: Setup, variable parameters and event configurations
are protected.
5: Program settings and all parameter settings are
protected.
[Description:]
PA02
can be displayed and changed regardless of
[Description:]
"-----"is displayed and setting cannot be performed.
1: ON
2: OFF
[Description:]
"-----"is displayed and setting cannot be performed.
0: AT not performed
1: Standard AT performed on currently used PID group
in mode other than READY mode.
2: AT writing overshoot-proof PID values to currently
used PID groups in mode other than READY mode
performed.
3: Standard AT performed on PID groups A1 to A7 in
READY mode.
4: AT writing overshoot-proof PID values to PID groups
A1 to A7 in READY mode continuously performed.
–5.0% to upper limit
[Description:]
Valid when setup data
Lower limit to +105%
[Description:]
Valid when setup data
–10000 to +10000 SPU
0.0 to 120.0sec
–1000 to +1000 PVU (PV1)
0.1 to 110.0% OUT/0.1sec
1 to 240sec
0 to +1000 SPU
–5.0 to +105.0%
[Description:]
"-----"is displayed and setting cannot be performed.
0.0 to 120.0sec
[Description:]
"-----"is displayed and setting cannot be performed on
model with one PV input channel.
–1000 to +1000 PVU (PV2)
[Description:]
"-----"is displayed and setting cannot be performed on
model with one PV input channel.
PA01
and
PA02
PA01
and
PA02
settings.
C21
setting is set to 1, 3, 5.
C21
setting is set to 1, 3, 5.
7-5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dcp550

Table of Contents