Chapter 7. PARAMETER SETUP
C93
(time proportional output system)
C95
(voltage output control)
7-30
0: Does not go on a second time off in time proportional cycle.
1: Goes on a second time in time proportional cycle.
• This setting determines whether the output is to go on again after the result of a PID
computation has changed in a time proportional cycle (cycle time) and the output has
been turned off.
• The difference between the two settings is illustrated below.
When set to 0
ON
OFF
PID computation
20%
result
When set to 1
ON
OFF
PID computation
20%
result
[Constant current type]
• Input current (maximum):
• Operating voltage range (input): Check that the voltage between the terminals of
This example shows the calculation for the connection of this unit and the
PGM10N015.
(Note: For connection with other model number, check the specifications of each
model.)
• Input current(maximum):
• Operating voltage range (input): The rating voltage is 3.5 to 30Vdc. Therefore,
Connection diagram
This unit
+
Cycle time
65%
40%
Cycle time
65%
40%
Check that the input current is within the
maximum allowable current or less, then the
parallel connection can be made.
the voltage pulse output is within the specified
range.
Since the input current is 10mA or less, up to
two units (10mA X 2 = 20mA < 24mA
[maximum allowable current]) can be
connected in parallel.
terminal voltage when terminals are opened, is
within the range.
+
PGM10N
Cycle time
Cycle time
+
PGM10N