8.2 Mains Supply

Mains supply (L1, L2, L3)
Supply voltage
Supply voltage
Supply voltage
Supply voltage
Mains voltage low/mains drop-out:
During low mains voltage or a mains drop-out, the frequency converter continues until the DC-link voltage drops below the
minimum stop level. Typically, this corresponds to 15% below the lowest rated supply voltage of the frequency converter. Power-
up and full torque cannot be expected at mains voltage <10% below the lowest rated supply voltage of the frequency converter.
Supply frequency
The frequency converter power supply is tested in accordance with IEC61000-4-28, 50 Hz +4/-6%.
Maximum imbalance temporary between mains phases
True power factor (λ)
Displacement power factor (cosφ) near unity
Switching on input supply L1, L2, L3 (power-ups) ≤7.5 kW (10 hp)
Switching on input supply L1, L2, L3 (power-ups) 11–90 kW (15–125 hp)
Environment according to EN 60664-1
8
8
The unit is suitable for use on a circuit capable of delivering not more than 100000 RMS symmetrical Amperes,
240/480/600/690 V maximum.

8.3 Motor Output and Motor Data

Motor output (U, V, W)
Output voltage
Output frequency
Switching on output
Ramp times
1) Dependent on power size.
Torque characteristics, normal overload
Starting torque (constant torque)
Overload torque (constant torque)
Torque characteristics, high overload
Starting torque (constant torque)
Overload torque (constant torque)
2) Percentage relates to the nominal torque of the frequency converter, dependent on power size.
64
®
VLT
AQUA Drive FC 202
Danfoss A/S © 10/2016 All rights reserved.
3.0% of rated supply voltage
≥0.9 nominal at rated load
Overvoltage category III/pollution degree 2
Maximum 110% for 1 minute, once in 10 minutes
Maximum 110% for 1 minute, once in 10 minutes
Maximum 150/160% for 1 minute, once in 10 minutes
Maximum 150/160% for 1 minute, once in 10 minutes
200–240 V ±10%
380–480 V ±10%
525–600 V ±10%
525–690 V ±10%
50/60 Hz +4/-6%
(>0.98)
Maximum 2 times/minute
Maximum 1 time/minute
0–100% of supply voltage
1)
0–590 Hz
Unlimited
1–3600 s
2)
2)
2)
2)
MG20MD02