5 Configuration of the system

5.5 Network Variable Description - VSD Profile - Output

5.5.1 Drive Speed
Variable
name:
nvoDrvSpeed
This variable contains the frequency converter speed as a percentage of the nominal speed.
5
5.5.2 Output Current
Variable
name:
nvoDrvCurnt
This variable contains the frequency converter output current in ampere measured as a mean value, IRMS.
The value is filtered and therefore approximately 1.3 seconds delayed before a current change is reflected in the output variable.
5.5.3 Output Voltage
Variable
name:
nvoDrvVolt
This variable contains the frequency converter output voltage.
5.5.4 Output Power
Variable
name:
nvoDrvPwr
This variable contains the frequency converter output power in kW, calculated on the basis of the actual motor voltage and current.
The value is filtered and therefore approximately 1.3 seconds delayed before a power change is reflected in the output variable.
5.5.5 Running Hours
Variable
name:
nvoDrvRunHours
This variable contains the total running hours of the motor.
36
SNVT
type:
SNVT_lev_percent
SNVT
type:
SNVT_amp
SNVT
type:
SNVT_volt
SNVT
type:
SNVT_power_kilo
SNVT
type:
SNVT_time_hour
MG.11.E2.02 - VLT
Value:
Min:
Max:
-163.840 %
+163.830 %
Value:
Min:
Max:
0 A
3,276.6 A
Value:
Min:
Max:
0 V
3,276.6 V
Value:
Min:
Max:
0 kW
6,554.4 kW
Value:
Min:
Max:
0 hr
65,534 hr
®
is a registered Danfoss trademark
VLT® FC 100 LonWorks
Resolution:
0.005 %
Resolution:
0.1 A
Resolution:
0.1 V
Resolution:
0.1 kW
Resolution:
1 hr