HVC 450 kW E-Bus Charger Installation Guide

4.4.2. Charge system configuration

4.4.3. AC power cable

Cable type: 3P+GND (optional shielded).
The cable shielding must be attached to the GND Rail at both ends of the cable.
The diameter of the cable conductor must be determined by your contractor.
The maximum diameter of the cable conductor is 240 mm
The GND conductor of the power cable must have the same diameter as the phase
conductors.

4.4.4. Cables between the Power Cabinets and the ACS Control Module

The following cables are not in the scope of supply of ABB.
6x DC power cables,
1x DC- OVP Sensing cable (between Junction Box and ACM)
1x GND cable,
1x AC utility power cable,
1x Interlock cable,
4x communication cables; 8x glass fiber (4 fibers are required, 4 are for spare).
 The 8x glass fiber cable is a special cable that will be supplied by ABB.
Revision: 1.2
Date released: 16-08-2018
2
(= 500 MCM)