Wiring; Safe Digital I/O - Safe Digital Inputs - SMC Networks EX245-FPS1 Operation Manual

Table of Contents

Advertisement

10.3. Wiring

Caution
●To prevent damage, all power for the SI Unit and modules must be turned off (i.e. de-energized) before
the modules are installed or removed.
●For a protection rating of IP65 to be ensured, sockets that are not used must be closed with M12 covering
caps.
●For a protection rating of IP65 to be ensured, all covering caps must be screwed down correctly after
wiring and setting have been performed.
Pin allocation of the M12, 5-way socket connector as shown in the following table:
Pin
1
2
3
4
5
Outer shell
WARNING: Loss of safety function
Parasitic voltages can result in the loss of the safety function.
●Connect the sensor ground directly to Pin 3 0V (US1) of the safety module. An external ground may not
be used.

10.4. Safe digital I/O - Safe digital inputs

Bit
Description
0
Input status of safe input 0
1
Input status of safe input 1
2
Input status of safe input 2
3
Input status of safe input 3
4
Input status of safe input 4
5
Input status of safe input 5
6
Input status of safe input 6
7
Input status of safe input 7
Note: In case of "1oo2 evaluation", input status of safe input 4-7 (Byte 0, bits 4 – 7) is fixed to 0: OFF
Table 10-4 Byte 1 Status bits (only applies to Safety Mode (Module Passivation/xxx))
Bit
Description
Status bit for
parameterization using
0
Safety Mode (Module
Passivation/xxx)
1 -7
Reserved
Byte 2-5: Reserved for PROFIsafe communication container specified by PROFIsafe.
Table 10-2 Safe input connectors
Allocation
UT1
DI (Input signal "n+4")
0V (US1)
DI (input signal "n")
UT2
FE (functional earth)
Table 10-3 Byte 0 Safe digital inputs
Connector No.
1
2
3
4
1
2
3
4
0: NOK (Fault state). SI unit has not received a process image for the
PROFIsafe parameters or the received process image is invalid
1: OK. Process image for PROFIsafe parameters received and valid.
-
- 53 -
View of connector (Module side)
2
5
1
3
4
Pin No.
Explanation
4
0: OFF, 1: ON
4
0: OFF, 1: ON
4
0: OFF, 1: ON
4
0: OFF, 1: ON
2
0: OFF, 1: ON
2
0: OFF, 1: ON
2
0: OFF, 1: ON
2
0: OFF, 1: ON
Explanation