Error codes for F parameter errors
Code
Additional Information
0x0040
None
64dez
0x0041
None
65dez
0x0042
None
66dez
0x0043
None
67dez
0x0044
None
68dez
0x0045
None
69dez
0x0046
None
70dez
Brief Description
The parameterised
F_destination_address
does not coincide with
Profisafe address on the safety module and value
the PROFIsafe
in the F_destination_address must be made to
address set on the
coincide.
safety module (F
module).
Invalid
parameterisation of the
F_destination_address.
Correct the value.
The addresses 0x0000
and 0xFFFF are not
permitted.
Invalid
parameterisation of the
F_source_address.
Correct the value.
The addresses 0x0000
and 0xFFFF are not
permitted.
Invalid
parameterisation of the
F_WD_time. A
Correct the value.
monitoring time of 0
ms is not permitted.
Invalid
parameterisation of the
F_SIL. The required
Use the device with the required SIL. The safety
SIL cannot be
module reaches SIL 3 as a maximum.
supported by the
safety module (F
module).
Invalid
parameterisation of the
F_CRC_length. The
CRC length generated
Check device description.
by the safety module
(F module) does not
correspond to the
required length.
F parameter set
version is invalid. The
version of the safety
Check device description.
module (F module)
Only V2 mode permitted.
does not coincide with
the required version.
- 97 -
Solution
No.EX##-OMY0004

Advertisement