4. General Specifications

Item
Rated voltage
Supply interruption for no loss of function
Protection class
Insulation resistance
Withstand voltage
Ambient temperature
Ambient humidity
Atmospheric pressure
Vibration resistance
Impact resistance
Operating environment
Certifications
EMC directive
Machinery directive
TUV Certification
PROFINET & PROFIsafe
UL
Table 4-1 EX245 series general specifications
24 V DC +20% -15%
1 ms maximum
IP65 (when fully installed or fitted with protective cover)
(complies with IEC 60529)
10 Mohm @ 500 VAC between FE and all accessible terminals to
IEC 61131-2.
500 VAC for 1 min. between FE and all accessible terminals to IEC
61131-2
Operation: -10 °C to 50 °C
Storage: -20 °C to 60 °C
35% to 85% RH (non-condensing)
Operation: 80 kPa to 108 kPa (under 2000 m)
Storage: 66 kPa to 108 kPa (under 3500 m)
10 Hz to 57 Hz (constant amplitude) 0.75 mm
57 Hz to 150 Hz (constant acceleration) 49 m/s
2 hours in each direction X, Y and Z
2
147 m/s
is applied 3 times in each direction X, Y and Z
EN 60068-2-27/29
No corrosive gas
Yes, 2014/30/EU, IEC61326-3-1
Yes, 2006/42/EC, EN 62061, EN ISO 13849
Yes, EN 61508, EN 62061, EN ISO 13849
Yes
Yes, for used materials (UL508)