Function
Parameter Name
Code
P0-09
Rotation direction
You can change the rotation direction of the motor just by modifying this parameter without
changing the motor wiring. Modifying this parameter is equivalent to exchanging any two of the
motor's U, V, W wires.
The motor will resume running in the original direction after parameter initialization. Do not
use this function in applications where changing the rotating direction of the motor is prohibited
after system commissioning is complete.
Function
Code
P0-10
When the frequency source is AI, pulse setting (DI5), or multi-reference, 100% of the input
corresponds to the value of this parameter.
The output frequency of the PE6000 can reach up to 3200 Hz. To take both frequency
reference resolution and frequency input range into consideration, you can set the number of
decimal places for frequency reference in P0-22.
If P0-22 is set to 1, the frequency reference resolution is 0.1 Hz. In this case, the setting range
of P0-10 is 50.0 to 3200.0 Hz.
If P0-22 is set to 2, the frequency reference resolution is 0.01 Hz. In this case, the setting
range of P0-10 is 50.00 to 600.00 Hz.
After the value of P0-22 is modified, the frequency resolution of all frequency related function
codes change accordingly.
Function
Code
Source of frequency upper
P0-11
Parameter Name
Maximum frequency
Parameter Name
limit
Setting Range
0: Same direction
1: Reverse direction
Note
Setting Range
50.00–600.00 Hz
Note
Setting Range
0: Set by P0-12 1: AI1
2: AI2
3: Keyboard potentiometer
4: Pulse setting (DI5)
5: Communication etting
83
Description of Function Codes
Default
50.00 Hz
Default
0
Default
0