Pioneer PE6000 Series User Manual page 119

Table of Contents

Advertisement

PE6000 User Manual
state.
During switchover between forward rotation and reverse rotation, the startup frequency holding
time is disabled. The holding time is not included in the acceleration time but in the running time of
simple PLC.
Example 1:
P0-03 = 0
P0-08 = 2.00 Hz
P6-03 = 5.00 Hz
P6-04 = 2.0s
In this example, the AC drive stays in the standby state and the output frequency is 0.00 Hz.
Example 2:
P0-03 = 0
P0-08 = 10.0 0 Hz
P6-03 = 5.00 Hz
P6-04 = 2.0s
In this example, the AC drive accelerates to 5.00 Hz, and then accelerates to the set frequency
10.00 Hz after 2s.
Function
Code
P6-05
Startup DC braking current/Pre-excited current
P6-06
Startup DC braking time/Pre-excited time
Startup DC braking is generally used during restart of the AC drive after the rotating motor
stops. Pre-excitation is used to make the AC drive build magnetic field for the asynchronous motor
before startup to improve the responsiveness.
Startup DC braking is valid only for direct start. In this case, the AC drive performs DC braking
at the set startup DC braking current. After the startup DC braking time, the AC drive starts to run. If
The frequency source is digital setting.
The digital setting frequency is 2.00 Hz.
The startup frequency is 5.00 Hz.
The startup frequency holding time is 2.0s.
The frequency source is digital setting.
The digital setting frequency is 10.00 Hz.
The startup frequency is 5.00 Hz.
The startup frequency holding time is 2.0s.
Parameter Name
119
Description of Function Codes
Setting Range
Default
0%–100%
0.0–100.0s
0.0s
0%