2.1.2 Main Circuit Terminals and Wiring
1) Description of main circuit terminals of single-phase AC drive
Terminal
Single-phase power supply
L1、L2
input terminals
(+)、(-)
Positive and negative
Connecting terminals of
(+)、PB
braking
U、V、W
AC drive output terminals
Grounding terminal
2) Description of main circuit terminals of three-phase AC drive
Terminal
Three-phase power supply
R、S、T
input terminals
Positive and negative
(+)、(-)
terminals of DC bus
Connecting terminals of
(+)、PB
braking resistor
Connecting terminals of
P、(+)
external reactor
U、V、W
AC drive output terminals
Grounding terminal
Figure 2-2 analog jumper of main board
Name
Name
Mechanical and Electrical Installation
Description
Connect to the single-phase 220 VAC power supply
Common DC bus input point
Connect to a braking resistor
Connect to a three-phase motor
Must be grounded
Description
Connect to the three-phase AC power supply
Common DC bus input point
Connect the external braking unit to the AC drive of
18.5 kW and above (220 V) and 37 kW and above
(other voltage classes).
Connect to the braking resistor for the AC drive of 15
kW and below (220 V) and 30 kW and below (other
voltage classes).
Connect to an external reactor.
Connect to a three-phase motor.
Must be grounded.
J3 AO1 output
Voltage and
Current
11
J4 A12 Input
J5 485 terminal
Voltage and
matched
Current
resistance