Description of Function Codes
P8-42
Setting Range
Timing duration source
P8-44
These parameters are used to implement the AC drive timing function.
If P8-42 is set to 1, the AC drive starts to time at startup. When the set timing duration is
reached, the AC drive stops automatically and meanwhile the corresponding DO becomes ON.
The AC drive starts timing from 0 each time it starts up and the remaining timing duration can
be queried by U0-20.
The timing duration is set in P8-43 and P8-44, in unit of minute.
AI1 input voltage lower limit
P8-45
AI1 input voltage upper limit
P8-46
When the AI1 input is larger than the value of P8-46 or smaller than the value of F8-45, the
corresponding DO becomes ON, indicating that AI1 input exceeds the limit.
P8-47
Module temperature threshold
Timing function
0
1
Setting Range
Setting Range
Setting Range
Default
Disabled
Default
0.0–6500.0 Min
Default
0.00 V to F8-46
Default
P8-45 to 10.00 V
Default
140
PE6000 User Manual
0
Enabled
0.0Min
3.10V
6.80V
75 °C