Description of Function Codes
For example, combining virtual DI/DO functions, to implement the function that the AC drive
reports an alarm when the actual accumulative power-on time reaches the threshold of 100 hours,
perform the setting as follows:
Set virtual DI1 to user-defined fault 1: A1-00 = 44.
Set that the valid state of virtual DI1 is from virtual DO1: A1-05 = 0000.
Set virtual DO1 to power-on time reached: A1-11= 24.
Set the accumulative power-on time threshold to 100 h: F8-16 = 100 h.
Then, the AC drive reports Err27 when the accumulative power-on time reaches 100 hours.
Accumulative running time
P8-17
It is used to set the accumulative running time threshold of the AC drive.
If the accumulative running time (P7-09) reaches the value set in this parameter, the
corresponding DO terminal becomes ON.
P8-18
Setting Range
This parameter is used to set whether to enable the safety protection.
If it is set to 1, the AC drive does not respond to the run command valid upon AC drive
power-on (for example, an input terminal is ON before power-on). The AC drive responds only after
the run command is cancelled and becomes valid again.
In addition, the AC drive does not respond to the run command valid upon fault reset of the AC
drive. The run protection can be disabled only after the run command is cancelled.
In this way, the motor can be protected from responding to run commands upon power-on or
fault reset in unexpected conditions.
Frequency detection value
P8-19
threshold
Setting Range
Startup protection
0
1
(FDT1)
Setting Range
Default
0–65000 h
Default
Default
0.00 Hz to maximum frequency
132
PE6000 User Manual
0h
0
No
Yes
50.00 Hz