PE6000 User Manual
P9-03
Overvoltage stall protective voltage
P9-04
When the DC bus voltage exceeds the value of P9-04 (Overvoltage stall protective voltage)
during deceleration of the AC drive, the AC drive stops deceleration and keeps the present running
frequency. After the bus voltage declines, the AC drive continues to decelerate.
P9-03 (Overvoltage stall gain) is used to adjust the overvoltage suppression capacity of the AC
drive. The larger the value is, the greater the overvoltage suppression capacity will be in the
prerequisite of no overvoltage occurrence, set F9-03 to a small value.
For small-inertia load, the value should be small. Otherwise, the system dynamic response will
be slow. For large-inertia load, the value should be large. Otherwise, the suppression result will be
poor and an overvoltage fault may occur.
If the overvoltage stall gain is set to 0, the overvoltage stall function is disabled.
The overvoltage stall protective voltage setting 100% corresponds to the base values in the
following table:
Voltage Class
Single-phase 220 V
Three-phase 220 V
Three-phase 380 V
Three-phase 480 V
Three-phase 690 V
Three-phase 1140 V
P9-05
Overcurrent stall protective voltage
P9-06
Overcurrent stall: When the output current exceeds the overcurrent stall protective current
Overvoltage stall gain
Setting Range
Setting Range
Overcurrent stall gain
Setting Range
Setting Range
Default
0 (no stall overvoltage)–100
Default
Corresponding Base Value
290 V
290 V
530 V
620 V
880 V
1380V
Default
Default
143
Description of Function Codes
0
130%
120% - 150%
20
0–100
150%