Operation, Display and Application Examples
Figure 3-18 AI as the Frequency Source
2. Figure 3-19 Current input of AI2 connected to 4DA module of the PLC as the frequency
source (4–20mA corresponding to 0–50 Hz)
Note
PE6000 provides two AI terminals (AI1 and AI2) on the control board, and the optional I/O
extension card provides another AI terminal (AI3).
AI1 provides 0–10 V voltage input. AI2 provides 0–10 V voltage input or 4–20mA current input,
determined by jumper J8 on the control board. AI3 provides -10 V to +10 V bipolar voltage input.
When AI is used as the frequency source, 100% of the voltage or current input corresponding
setting corresponds to the maximum frequency in P0-10.
When the temperature transmitter is used for analog setting, it must be connected to AI3 on
the I/O extension card.
PE6000 provides five corresponding relationship curves, which can be selected in P4-33. The
input values and corresponding settings of each curve are set in F4-13 to P4-27 and group A6.
P4-16
P4-13 = 0.00V
P4-14 = 0.0%
P4-15 = 10.00V
P4-16 = 100%
P4-14
P4-17 = 0.1s
P4-33
P4-13
P4-18 = 0.00V
P4-19 = 0.0%
P4-20 = 10.00V
P4-21 = 100%
P4-22 = 0.1s
30
P4-33 = 1
P0-10 = 50.00Hz
P4-13
P4-15
P4-17
P4-33=10
P0-10=50.00Hz
P4-21
P4-19
P4-18
P4-20
P4-33
P4-18
P4-22
PE6000 User Manual
P0-07 = 0
P0-03 = 2
P0-07=0
P0-03=2