Response delay
Pd-03
Setting range
Response delay: the interval between AC drive receiving data and upper computer sending
data. If response delay is less than system processing time, the latter serves as response delay. If
response delay is more than system processing time, after the system processing, upper computer
will not send data until the response delay time.
Communication
Pd-04
Setting range
If the function code is set at 0.0s, the communication timeout is invalid.
When the function code is set at valid value, the system will generate communication fault
(Err16) if the interval between communications exceeds communication timeout. In general, the
parameter is set at 0.0s. In continuous communication, the parameter is used to monitor
communication situation.
Communication
protocol selection
Pd-05
Setting range
Fd-05=1: Select standard Modbus protocol
Fd-05=0: If the number of bytes that returned to the slave is more than the standard Modbus
protocol, refer to Section 5 Communication Data Structure in the protocol.
Resolution While
reading current
Pd-06
Setting range
It is used to ensure the output unit of current value while reading output current.
timeout
0:non-standard Modbus protocol
1:standard Modbus protocol
default
0-20ms
default
0.0s (invalid):0.1-60.0s
Default
default
0: 0.01A: 1: 0.1A
207
Appendix B
2ms
0.0s
0
0