Description of Function Codes
U0-18
Input pulse frequency
It displays the high-speed pulse sampled frequency of DI5, in minimum unit of 0.01 kHz.
U0-19
It displays the actual output frequency of the AC drive.
If P0-22 (Frequency reference resolution) is set to 1, the display range is -3200.00–3200.00Hz.
If P0-22 (Frequency reference resolution) is set to 2, the display range is -320.00Hz–320.00Hz.
U0-20
Remaining running time
It displays the remaining running time when the timing operation is enabled. For details on
timing operation, refer to P8-42 to P8-44.
U0-21
AI1 voltage before correction
AI2 voltage (V)/ current (mA)
U0-22
They display the AI sampleding voltage/current value of AI.
The actually used voltage/ current is obtained after linear correction to reduce the deviation
between the sampled voltage/current and the actual input voltage/current.
For actual corrected voltage, see U0-09, U0-10 and U0-11. Refer to group AC for the correction
mode.
U0-24
It displays the linear speed of the DI5 high-speed pulse sampling.
The unit is meter/minute. The linear speed is obtained according to the actual number of pulses
sampled per minute and PB-07 (Number of pulses per meter).
U0-27
Pulse input frequency
It displays the DI5 high-speed pulse sampling frequency, in minimum unit of 1 Hz. It is the
same as U0-18, except for the difference in units.
Feedback speed
before correction
Linear speed
Display Range
Display Range
Display Range
Display Range
Display Range
Display Range
Display Range
182
PE6000 User Manual
0.00–100.00 kHz
-320.00–320.00 Hz
-3200.0–3200.0 Hz
0.0–6500.0 min
0.00–10.57 V
0.00–10.57 V
0.00–20.00 mA
0–65535 m/min
0–65535 Hz