Operation, Display and Application Examples
`Figure 3-5 Setting of using the electromagnetic button for start/stop
Control switch
Forward
Stop
Reverse
In the preceding figure, when SB1 is ON, the AC drive instructs forward rotation; when SB1 is
OFF, the AC drive stops. When SB2 is ON, the AC drive instructs reverse running; when SB2 is
OFF, the AC drive stops. If SB1 and SB2 are ON or OFF simultaneously, the AC drive stops.
3.6.1.3 Communication Control
The host computer controls the AC drive to communicate with PE6000 through RS485 in
communication code. Interaction between the PE6000 with the user programmable card is also
by means of communication.
Install a matching communication card in the multifunction extension port, and set P0- 02 to 2.
Then, you can start or stop the AC drive in communication mode. The following figure shows the
setting method.
Host
computer
When PD-04 is set to a non-zero number, the function of automatic AC drive stop upon
communication timeout is enabled. This prevents uncontrollable AC drive running due to faults of
the communication cable or the host computer.
The communication port of the AC drive supports the Modbus-RTU protocol, and the
communication is implemented only when the host computer supports the Modbus- RTU master
Function
Terminal
code
Communication setting should be
in line with host computer setting
RS485
Communication
Pd-00: Communication rate
card
Pd-01: Validation
Pd-02: Address
Pd-03: Answering delay
Pd-04: Communication timeout
Pd-06: Transformation Format
Setting value Terminal control
Forward
Reverse
Stop
Three-line mode 1
Set command source as
communication mode
22
PE6000 User Manual
Command
source selection
Running
command
Terminal control
Run
command