Pioneer PE6000 Series User Manual page 78

Table of Contents

Advertisement

Description of Function Codes
Function
Code
P0-02
It is used to determine the input channel of the AC drive control commands, such as run,
stop, forward rotation, reverse rotation and jog operation. You can input the commands in the
following three channels:
0: Operation panel control ("LOCAL/REMOT" indicator off). Commands are given by pressing
keys Run and Stop on the operation panel
1: Terminal control ("LOCAL/REMOT" indicator on)
Commands are given by means of multifunctional input terminals with functions such as
FWD, REV, JOGF, and JOGR.
2: Communication control ("LOCAL/REMOT" indicator blinking)
Commands are given from host computer. Please refer to communication parameters of
Group P and Group D to get function parameters for communication. Refer to the additional
instructions of corresponding communication card. An brief instruction of communication card is
attached in the Appendix of the Brochure.
Function
Parameter Name
Code
Main frequency source
P0-03
It is used to select the setting channel of the main frequency. You can set the main frequency in
the following 10 channels:
0: Digital setting (non-retentive at power failure)
The initial value of the set frequency is the value of P0-08 (Preset frequency). You can
Parameter Name
Command
source selection
X selection
Setting Range
0: Operation panel control (LED off)
1: Terminal control (LED on)
2: Communication control (LED blinking)
Setting Range
0: Digital setting (preset frequency P0-08,
UP/DOWN modifiable, non-retentive at
power failure)
1: Digital setting (preset frequency P0-08,
UP/DOWN modifiable, retentive at power
failure)
2: AI1
3: AI2
4: Keyboard potentiometer
5: Pulse setting (DI5)
6: Multi-reference
7: Simple PLC
8: PID
9: Communication setting
78
PE6000 User Manual
Default
0
Default
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents