Mechanical and Electrical Installation

2 Mechanical and Electrical Installation

2.1 Mechanical Installation

2.1.1Installation Environment Requirements
1) Ambient temperature: Ambient temperature has great impact to product's service life, so the
operation temperature should be within -10°C -50°C.
2) Install the AC drive on the surface of an incombustible object, and ensure that there is
sufficient space around for heat dissipation.
3) Vibration should be less than 0.6g. Far away from the punching machine or the like
4) Free from direct sunlight, high humidity and condensation
5) Free from corrosive, explosive and combustible gas
6) Free from oil dirt, dust and metal powder
Figure 2-1 Installation of PE6000
Single AC drive: When the power of AC drive is less than 22KW, there is no demand for A
dimension. If the power is more than 22KW, A dimension should be more than 50mm.
Multiple AC drive: For application installing multiple AC drives, if one row of AC drives need to
be installed above another row, install an insulation guide plate.
Power class
≤15kW
18.5kW—30kW
≥37kW
Installation Dimension
B
≥100mm
≥200mm
≥300mm
10
PE6000 User Manual
A
No request
≥50mm
≥50mm