Description of Function Codes
Value
Function
Frequency lower limit
37
reached (having
output at stop)
38
Alarm output
Current running time
40
reached
41
Fault Output
Function
Code
P5-06
P5-07
The output pulse frequency of the FMP terminal ranges from 0.01 kHz to "Maximum FMP
output frequency" (P5-09). The value of P5-09 is between 0.01 kHz and 100.00 kHz.
The output range of AO1 and AO2 is 0–10 V or 0–20 mA. The relationship between pulse and
analog output ranges and corresponding functions is listed in the following table.
Table Relationship between pulse and analog output ranges and corresponding functions
Value
0
1
2
3
Output torque (absolute value)
4
5
6
7
8
11
12
Communication setting
If the running frequency reaches the lower limit, the
terminal becomes ON. In the stop state, the signal is still
ON.
If a fault occurs on the AC drive and the AC drive
continues to run, the terminal outputs the alarm signal.
If the current running time of AC drive exceeds the value
of 8-53, the terminal becomes ON.
Fault output is the fault of coasting to stop and no output
in occasion of under voltage.
Parameter Name
FMP function selection
AO1 function selection
Function
Running frequency
Set frequency
Output current
Output power
Output voltage
Pulse input
AI1
AI2
Count value
Description
Range (Corresponding to Pulse or Analog
Output Range 0.0%–100.0%)
0 to maximum output frequency
0 to maximum output frequency
0 to 2 times of rated motor current
0 to 2 times of rated motor torque
0 to 2 times of rated power
0 to 1.2 times of rated AC drive voltage
0.01–100.00 kHz
0–10 V
0–10 V (or 0–20mA)
0 to maximum count value
0.0%–100.0%
116
PE6000 User Manual