Description of Function Codes
Function
Code
PB-01
PB-02
This parameter is used to determine the swing amplitude and jump frequency amplitude.
If relative to the central frequency (PB-00 = 0), the actual swing amplitude AW is the calculation
result of F0-07 (Frequency source selection) multiplied by PB-01.
If relative to the maximum frequency (PB-00 = 1), the actual swing amplitude AW is the
calculation result of F0-10 (Maximum frequency) multiplied by PB-01.
Jump frequency = Swing amplitude AW x PB-02 (Jump frequency amplitude).
If relative to the central frequency (PB-00 = 0), the jump frequency is a variable value.
If relative to the maximum frequency (PB-00 = 1), the jump frequency is a fixed value.
The swing frequency is limited by the frequency upper limit and frequency lower limit.
Function
Code
PB-03
PB-04
Triangular wave rising time coefficient
PB-03 specifies the time of a complete swing frequency cycle.
PB-04 specifies the time percentage of triangular wave rising time to PB-03 (Swing frequency
cycle).
Triangular wave rising time = PB-03 (Swing frequency cycle) x PB-04 (Triangular wave rising
time coefficient, unit: s)
Triangular wave falling time = PB-03 (Swing frequency cycle) x (1 – PB-04 Triangular wave
rising time coefficient ,unit: s)
Function
Code
PB-05
PB-06
PB-07
The preceding parameters are used for fixed length control.
The length information is collected by DI terminals. PB-06 (Actual length) is calculated by
Parameter Name
Swing frequency amplitude
Jump frequency amplitude
Parameter Name
Swing frequency cycle
Parameter Name
Set length
Actual length
Number of pulses per meter
Setting Range
0.0%–100.0%
0.0%–50.0%
Setting Range
0.0–3000.0s
0.0%–100.0%
Setting Range
0–65535 m
0–65535 m
0.1–6553.5
158
PE6000 User Manual
Default
0.0%
0.0%
Default
10.0s
50.0%
Default
1000 m
0 m
100.0