Page 3
& I NSTRUCTIONS FOR IGHT NFLEXION Warranty ® Will-Burt warrants its Night Scan to be free from defects in material and workmanship for a period of two (2) years, with such time period running from the date of shipment by Will-Burt. Will-Burt shall not be responsible for any damage resulting to or caused by its products by reason of failure to properly install, maintain or store the product;...
Page 4
& I NSTRUCTIONS FOR IGHT NFLEXION Document History Document Numbers Dates Remarks TP-5554501-00 2/11/2019 Initial Release TP-5554501-A 2/28/2019 Updated Section 2.6.2 and 5.4. TP-5554501-B 5/01/2019 General Updates/Add Inflexion HD Original Instructions TP-5554501-B May 2019...
& I NSTRUCTIONS FOR IGHT NFLEXION Table of Contents Safety Summary ........................vii Signal Word Definitions ..........................vii General Safety Instructions ........................vii Symbols ..............................x Section 1 Introduction ......................1-1 1.1 Intended Use ............................ 1-1 1.2 Specification Compliance ......................... 1-2 1.2.1 CE Declaration of Conformity ....................
Page 6
NFLEXION 2.6.1 Physical Installation Detailed Instructions ................. 2-9 2.6.1.1 Select a Suitable Mounting Location................2-10 2.6.1.2 Unpack the Night Scan Lite/Inflexion HD ................. 2-10 2.6.1.3 Secure the Mast Assembly ....................2-12 2.6.1.4 Secure the Junction Box ....................2-13 2.6.1.5 Install Additional Accessories (Optional)................2-13 2.6.2 Electrical Installation Detailed Instructions ................
Page 7
Figure 2-5 Permissible Sling Points ......................2-11 Figure 2-6 Mast Assembly Mounting Holes .................... 2-12 Figure 2-7 Night Scan Lite System Customer Wiring Overview (Not to Scale) ........2-14 Figure 2-8 Grounding Lug Location ......................2-14 Figure 2-9 Night Scan Lite Power Relay Wiring Diagram ............... 2-15 Figure 2-10 Night Scan Lite Main Control Board Wiring Diagram ............
Page 8
NFLEXION Table of Tables Table 1-1 Night Scan Lite with RCP and Four X200 LED Lights .............. 1-6 Table 1-2 Night Scan Lite with RCP and Two X200 LED Lights .............. 1-7 Table 1-3 Night Scan Lite with RCP and No Lights .................. 1-8 Table 1-4 Inflexion HD (No RCP/No Lights) .....................
NFLEXION Safety Summary This section describes safety precautions for the Night Scan Lite and Inflexion HD. These are recommended precautions that personnel must understand and apply throughout many phases of installation, operation, transportation, maintenance, storage, and troubleshooting. Be sure to read and understand the entire manual and contact The Will-Burt Company with any questions, before performing any procedure outlined in this manual.
Page 10
& I NSTRUCTIONS FOR IGHT NFLEXION Relocation/Driving Hazard! Do not relocate the system during operation or while the mast is extended to any height above the nested position or powered up. Do not move vehicle until the mast has been securely nested and isolated from power. Power-up and operate the mast only if the vehicle is stationary and securely parked with the parking brake properly applied.
Page 11
& I NSTRUCTIONS FOR IGHT NFLEXION Radiation Hazard – Do not look at lights! Do not look directly into lights when they are illuminated. Temporary impairment or permanent vision damage could occur. Freezing/Burn Hazard! Make sure the lights are completely cool before attempting to clean or perform maintenance.
& I NSTRUCTIONS FOR IGHT NFLEXION Symbols The following are symbols that are used with the system and their meaning. Contact The Will- Burt Company with any questions before performing any procedure outlined in this manual. This symbol indicates an electrocution hazard or hazardous voltage hazard. Contact with high voltage will result in death or serious injury.
Views are not to scale. This manual describes installation, operation, transportation, maintenance, and troubleshooting procedures for the Night Scan Lite™ and Inflexion HD™. This manual assumes the use of a standard catalog Night Scan Lite or Inflexion HD. Procedures and characteristics for systems customized to meet customer needs may vary.
& I NSTRUCTIONS FOR IGHT NFLEXION 1.2.2 National Fire Protection Agency NFPA 1901:2016 Compliance The mast system is designed to be compliant with the following sections of NPFA-1901 2016 Edition: 22.14 Powered Operated Light Masts 23.13 Power Operated Masts To adhere to NFPA requirements, the installer shall do the following during installation: 1.
“Mast” to refer to the mechanical folding mast (Night Scan Lite and Inflexion HD). “Mast System” to refer to the entire Night Scan Lite or Inflexion HD Mast System (Mast Assembly, Junction Box, Hand-Held Remote Control, and Junction Box Cable).
& I NSTRUCTIONS FOR IGHT NFLEXION Table 1-1 Night Scan Lite with RCP and Four X200 LED Lights Functional Characteristic Specification* Fully Extended Height to top of Lights 2307 mm (90.8 inches) Fully Extended Height to top of Top Section 2000 mm (78.7 inches)
& I NSTRUCTIONS FOR IGHT NFLEXION Table 1-2 Night Scan Lite with RCP and Two X200 LED Lights Functional Characteristic Specification* Fully Extended Height to top of Lights 2,234 mm (88 inches) Fully Extended Height to top of Top Section 2,000 mm (78.7 inches)
& I NSTRUCTIONS FOR IGHT NFLEXION Table 1-3 Night Scan Lite with RCP and No Lights Functional Characteristic Specification* Fully Extended Height to top of RCP 2,228.5 mm (87.8 inches) Fully Extended Height to top of Top Section 2,000 mm (78.7 inches) Fully Nested Height 368 mm (14.5 inches)
This section describes major components of a Mast System assuming the use of standard catalog Mast Systems. Characteristics of components customized to meet customer-specific needs may vary. If necessary, contact The Will-Burt Company for additional details. Major components of the Night Scan Lite include (Figure 1-1): Mast Assembly o X200 Lights (P/N: 5355406) (Section 1.7.1.1)
& I NSTRUCTIONS FOR IGHT NFLEXION 1.7.1 Mast Assembly The folding Mast Assembly (Figure 1-1): Is used to raise the payload to the operational height of two meters (78.7 inches) Extends and retracts electro-mechanically Is made predominately of steel ...
& I NSTRUCTIONS FOR IGHT NFLEXION 1.7.1.1 X200 Lights (P/N: 5355406) The standard light options for the Night Scan Lite are: (4) X200 LED Lights (2) X200 LED Lights No Lights The X200 LED Lights (Figure 1-2) are: ...
& I NSTRUCTIONS FOR IGHT NFLEXION 1.7.1.3 RCP Cable The RCP cable routs through the Top Section across the Knuckle and through the Base Section to the Control Box. Cable Conduit protects the RCP as it routs across the Knuckle. There is no coiled cable in the system.
& I NSTRUCTIONS FOR IGHT NFLEXION 1.7.1.6 Support Struts The Support Struts (Figure 1-4) provide lateral stability to the lift mechanism in all operating positions. Support Struts Springs Actuator Figure 1-4 Support Struts, Actuator, and Gas Springs 1.7.1.7 Actuator (P/N: 5467502) The Actuator (Figure 1-4): ...
& I NSTRUCTIONS FOR IGHT NFLEXION 1.7.1.9 Base The Base (Figure 1-5): Is made of steel Has eight mounting holes to section the Mast System to the mounting location Has a spring in the base pivot join to remove mechanical play in the Base Section and create a stable platform Saddle (Side-to-Side Support)
& I NSTRUCTIONS FOR IGHT NFLEXION 1.7.1.11 Control Box Assembly (P/N: 5551801) The Control Box Assembly (Figure 1-6): Prevents RCP motion or lights until the mast reaches full extension height Provides two auxiliary power inputs (10 amp maximum) that are disabled until the mast is fully extended ...
System. These labels come installed on the Mast System. Additionally, an Operation Label (P/N: 5555101) ships loose with the Mast System for Night Scan Lite. This label shall be applied where the operator can view during operation. The Operation Label is required for NFPA1901 compliance.
& I NSTRUCTIONS FOR IGHT NFLEXION 1.7.3 Hand-Held Remote Control (HHRC) (P/N: 5547101) The HHRC (Figure 1-9): Is tethered with a 3 meter (10 foot) long cable to the Junction Box Uses momentary switches for all motion Is IP54 rated for dust and water ingress protection Figure 1-9 Hand-Held Remote Control 1.7.4 Junction Box Cable (P/N: 218103 cut to specified length or P/N:...
& I NSTRUCTIONS FOR IGHT NFLEXION 1.7.5 Accessory Options (Sold Separately) This section describes accessory options available for the Night Scan Lite as follows: Strobe/Beacon Lights (Section 1.7.5.1) Cameras (Section 1.7.5.2) 1.7.5.1 Strobe/Beacon Lights The optional strobe/beacon lights: ...
Page 32
& I NSTRUCTIONS FOR IGHT NFLEXION 1-20 Original Instructions TP-5554501-B 2019...
& I NSTRUCTIONS FOR IGHT NFLEXION Section 2 Installation This section describes the installation of the system and provides general procedures that must be followed to ensure a successful installation. Use care to understand and follow all precautions while installing. 2.1 Pre-Installation Check Before installing the system, ensure: ...
& I NSTRUCTIONS FOR IGHT NFLEXION Equipment Damage – Qualified Personnel! All persons installing and maintaining this equipment should be suitably qualified and work to local, regional, and national standards and codes of practice. Safety Instruction – Roof Access! If mast will be mounted to a vehicle, the operator must provide safe means to access the roof of the vehicle during installation and maintenance.
Table 2-2 Installation Hardware Hardware* Supplied By Notes Base of Night Scan Lite (To the Mounting Structure) (8) Sets of M14 Customer The bolts should be sized to length to allow for (minimum) to M16 (⅝...
& I NSTRUCTIONS FOR IGHT NFLEXION 2.5 Power Supply Requirements The mast control system: Requires a 20-30 VDC power supply for the mast control system Requires 10 AWG Wire (6 mm ) or heavier power cable with maximum length of 15 meters (50 ft.), 10/2 SJOW cable or equivalent ...
These instructions assume that the mounting hole locations are not pre-drilled and that the Night Scan Lite or Inflexion HD components will be used as templates to drill these holes during installation. Alternatively, the mounting hole location could be found and pre-drilled using the installation dimensions (Section 2.4).
Junction Box to HHRC o Customer Power to Control Box 2.6.1.2 Unpack the Night Scan Lite/Inflexion HD During installation, it will be necessary to lift the mast. The process described in this manual represents a possible method of lifting the mast. Depending on the environment and equipment available, other methods may work better.
& I NSTRUCTIONS FOR IGHT NFLEXION Unpack the system as follows: 1. Carefully open the shipping crate. 2. Inspect for any shipping damage. Notify the carrier if damage is evident. 3. Remove all loose components. 4. Outfit the mast with a sling and hoist capable of supporting the mast weight. The sling must support the mast from as least three points.
& I NSTRUCTIONS FOR IGHT NFLEXION 2.6.1.3 Secure the Mast Assembly To secure the Mast Assembly: 1. Carefully move the Mast Assembly into position in the mounting location. 2. Use the Base of the Mast Assembly as a template to drill eight mounting holes (Figure 2-6) into the mounting structure.
The recommended installation torque for M6 Stainless Steel bolts is 7-8 Nm (5-6 ft-lb.). Note: An Operation Label (P/N: 5555101) ships loose with the Mast System for Night Scan Lite. This label includes important warning symbols also located on the Mast Assembly. This label shall be applied in a location visible to the operator while operating the mast system.
NFLEXION 2.6.2 Electrical Installation Detailed Instructions The following are detailed steps describing the electrical installation of the Night Scan Lite and Inflexion HD. The exact installation procedures may vary based on the configuration of the system being used and the installation environment. Use the best and safest method for your circumstances.
& I NSTRUCTIONS FOR IGHT NFLEXION The Control Box Assembly: Is located underneath the RCP when the mast is fully nested. Has eight locations with cable grips for cables used as described in Figure 2-12. Control Box Control Box Assembly Contains Assembly...
& I NSTRUCTIONS FOR IGHT NFLEXION 4. Once the screw is removed, insert the drive flexible extension with a 6mm hex bit long enough to engage the manual override shaft in the back of the actuator. Crank counterclockwise with a manual ratchet wrench to extend the mast. Once the mast is raised enough to insert a standard hex wrench, a standard hex wrench can be used.
9. Tighten the cable grip ensuring there is adequate slack inside the control box. 2.6.2.3 Wire Vehicle Interlock on Sensor The Night Scan Lite and Inflexion HD is designed to allow for integration into vehicle safety circuitry to eliminate the possibility of driving with the mast extended. Usage shall be used to comply with various safety standards such as NFPA-1901.
& I NSTRUCTIONS FOR IGHT NFLEXION position, adjust the sensor 1 mm closer to the moving base section and tighten the nut to 67-80 N·m. Ensure the lock washer is seated on both sides. The end of the sensor should be approximately 5 mm away from the moving base section after adjustment.
& I NSTRUCTIONS FOR IGHT NFLEXION Figure 2-16 Vehicle Interlock Circuit Wiring Diagram 2.6.2.4 Wire Optional Auxiliary Devices to Power Relay Board Depending on the configuration of your system, there may be additional auxiliary devices installed such as a strobe or beacon light, or a camera. The Power Relay Board allows for up to two auxiliary devices to be installed with a maximum amp draw of 10 amps per device.
& I NSTRUCTIONS FOR IGHT NFLEXION 1. Run a 14 AWG (2.5 mm ) wire from the auxiliary device to the Control Box Assembly. 2. Locate terminal block TB6 on the Power Relay Board (P/N: 5553301). 3. Secure the wire to TB6 at either AUX 1 or AUX 2 as shown in Figure 2-17. Figure 2-17 Power Relay Board Terminal Block TB6 2.6.2.5 Wire Power for Optional Auxiliary Devices to Power Relay Board If an auxiliary device is installed on the system, customer fused or breaker protected power will...
& I NSTRUCTIONS FOR IGHT NFLEXION 2.6.2.6 Wire Power for Lights or Payload to Power Relay Board The X200 LED lights can use a 20-30 VDC power supply. The customer should supply fused or breaker-protected power for the lights or alternate payload. Each light bank or payload can have up to a 20 amp draw per side or 40 amps total.
& I NSTRUCTIONS FOR IGHT NFLEXION Follow the routing instructions in Figure 2-20 for the RCP cable to install cabling for Inflexion HD payloads. Figure 2-20 Payload Cable Routing OPTIONAL 12 VDC SUPPLY: The following information defines how to power the Mast System with a 10-15 VDC power supply (battery).
& I NSTRUCTIONS FOR IGHT NFLEXION Figure 2-21 12VDC Input Power Wiring 2.6.2.7 Wire Power for Mast and Control to Power Relay Board The mast and control require a 20-30 VDC power supply with a nominal power of 24 VDC. The system may have an amp draw of up to 20 amps.
& I NSTRUCTIONS FOR IGHT NFLEXION 4. Tighten the cable grip ensuring proper slack inside the control box. See Section 2.6.2.6 for optional powering with 10-15 VDC power supply. 2.6.2.8 Finalize Electrical Installation To finalize the electrical installation: 1. Ensure all wiring is complete. 2.
NSTRUCTIONS FOR IGHT NFLEXION 2.7 Test the Installation Follow all precautions while testing the Night Scan Lite or Inflexion HD installation. To test the installation: 1. Review the Pre-Operation Check (Section 3.1). 2. Initiate the System (Section 3.4.2.1). 3. Extend the mast (Section 3.4.2.2).
) minimum) needs to be added as noted above to allow the mast to retract. The Night Scan Lite with RCP will arrive with the payload saddles factory adjusted. For the Inflexion HD with other payloads, the installer shall ensure the payload is secure from shock and vibration damage in the nested position during vehicle transport.
Page 62
& I NSTRUCTIONS FOR IGHT NFLEXION 2-30 Original Instructions TP-5554501-B 2019...
& I NSTRUCTIONS FOR IGHT NFLEXION Section 3 Operation This section describes operation of the system. The exact operating procedures will vary based on the configuration of your system. Follow the appropriate operation procedures for your system. Use care to understand and follow all precautions while operating. 3.1 Pre-Operation Check Before operating the system, ensure: ...
& I NSTRUCTIONS FOR IGHT NFLEXION Safety Instruction – Operation! Mast is recommended for outdoor operation. If used indoors, ensure overhead area is free of power lines or other overhead obstructions. Do not use in areas that have been classified as hazardous as defined in Article 500 of the National Electric Code (United States).
& I NSTRUCTIONS FOR IGHT NFLEXION 3.3 Controls The following controls are available on your system: Symbol Name Function Provides an emergency stop of the system when pressed. All mast and RCP motion will stop and the system powers down. Emergency Stop Switch Emergency Stop Switch must be twisted and pulled to enable...
& I NSTRUCTIONS FOR IGHT NFLEXION 3.4 Operation This section describes operation of the Mast System using powered operation. If an emergency stop is required at any time, press the Emergency Stop Switch on the Junction Box. All mast and RCP motion will stop. If an emergency stop event occurs, after actuation and before disengaging the emergency stop, the mast system shall be inspected in order to detect the reason for the actuation.
& I NSTRUCTIONS FOR IGHT NFLEXION 4. Press the Start button, on the Junction Box, to initiate system power. The power LED (Figure 3-1) on the HHRC will turn green when the system is powered. Power Figure 3-1 Power LED Note: If the system is powered and stays nested with no other commands, the system will power off after 60 seconds of inactivity.
& I NSTRUCTIONS FOR IGHT NFLEXION 3.4.2.3 Operate the RCP and Lights All RCP, AUX and Light functions are prohibited by the control until the mast has reached the fully extended height. Attempts to pan and tilt the RCP while at an intermediate height are prohibited by the control to protect the lights or payload from crashing into the vehicle while deploying or retracting.
& I NSTRUCTIONS FOR IGHT NFLEXION 3.4.2.5 Retract the Mast To retract the mast: 1. Press and hold the Mast Down button until the mast reaches the fully nested position and all mast motion stops. When the Mast Down button is pressed and held, the RCP will automatically home itself, if it is not already in the home position, before allowing the mast to lower.
& I NSTRUCTIONS FOR IGHT NFLEXION 3.4.3 Manual Operation of the Mast Safety Instruction – Pinching/Crushing Hazard! Never manually operate the mast while power is still applied to the system. Ensure the Mast System is de-energized and the power isolation procedure is followed. Any attempt to electrically energize the Mast System when manually operating the mast may result in injury.
& I NSTRUCTIONS FOR IGHT NFLEXION Section 4 Transportation Before transporting the system, the system needs to be secured. The exact procedures for transportation will vary based on the system configuration. The process described in this manual represents a possible method of transporting the mast. Depending on the environment and equipment available, other methods may work better.
& I NSTRUCTIONS FOR IGHT NFLEXION 4.2 Shipping When shipping the system, The Will-Burt Company recommends shipping the mast in the original shipping crate (P/N: 5567801). If the original shipping crate is not available, contact The Will-Burt Company to order a replacement. Safety Instruction –...
& I NSTRUCTIONS FOR IGHT NFLEXION Section 5 Maintenance This section describes maintenance procedures required to keep the system operational Use care to understand and follow all precautions while performing these procedures. 5.1 Pre-Maintenance Check Before performing maintenance procedures, ensure the following precautions are understood and followed: Trained Personnel Only! Only trained and qualified personnel should perform maintenance and servicing procedures.
& I NSTRUCTIONS FOR IGHT NFLEXION 5.2 Power Isolating Procedure All power sources shall be removed from the mast system including mast controls, lighting power, auxiliary device power before performing any maintenance operation on the mast system. To isolate power to the mast system: 1.
& I NSTRUCTIONS FOR IGHT NFLEXION 5.4 Spare Parts To order spare or replacement parts, always refer to the mast model number and serial number. The model number, serial number, and additional information is engraved on the mast Identification Plate. Throughout this manual, “P/N” followed by a number represent the part number for that component.
Page 76
& I NSTRUCTIONS FOR IGHT NFLEXION Frequency Inspection Action Fasteners – Inspect external Monthly Replace any missing or damage fasteners, shaft safety pins, snap hardware. If any hardware is found rings, and actuator coupling pin loose, retighten. If loose fasteners retaining clip.
Page 77
& I NSTRUCTIONS FOR IGHT NFLEXION Frequency Inspection Action Side Saddle Adjustment – Attempt Monthly If side-to-side play is observed to move the top tube or RCP side-to- greater than 1/16 inches (1.5 mm), side in the saddle in the mast nested adjust the saddle plates to reduce position.
& I NSTRUCTIONS FOR IGHT NFLEXION 5.6 Cleaning the System Health and Safety Hazard! Solvent used to clean parts is potentially dangerous. Follow solvent manufacturer’s safety procedures and recommendations. Avoid inhalation of fumes and also prolonged contact to skin. Death or serious injury could occur if solvents are not handled properly.
& I NSTRUCTIONS FOR IGHT NFLEXION Section 6 Troubleshooting This section describes troubleshooting for the Mast System. Use care to understand and follow all precautions while troubleshooting the Mast System. TP-5554501-B Original Instructions May 2019...
& I NSTRUCTIONS FOR IGHT NFLEXION 6.1 Adjust RCP Saddles The saddles are adjusted in the factory for new masts. Over time, vibration during transportation and wear may cause the RCP and payload to bounce excessively. If excessive bouncing is observed, the RCP saddles (Figure 6-1) may be adjusted upwards to cause the RCP to sit tighter on the saddle in the nested position.
& I NSTRUCTIONS FOR IGHT NFLEXION To adjustment the RCP saddle heights: 1. Ensure the mast is in the nested position with the RCP resting on the saddles. 2. Ensure power is removed from the system according to the Power Isolating Procedure (Section 5.2.) 3.
Page 82
& I NSTRUCTIONS FOR IGHT NFLEXION Original Instructions TP-5554501-B 2019...
& I NSTRUCTIONS FOR IGHT NFLEXION Section 7 Reference This section provides reference information for the system as follows: Extended Glossary of Terms (Section 7.1) Disposal of Mast System (Section 7.2) 7.1 Extended Glossary of Terms This section describes general terms and abbreviations used within this manual. ...
IGHT NFLEXION “Mast System” to refer to the entire Night Scan Lite Mast System (Mast Assembly, Junction Box, Hand-Held Remote Control, and Junction Box Cable). “Nested” refers to the position of the mast were the mast sections have not extended (Figure 7-2).