GE DigitalFlow XGS868i Programming Manual page 133

Panametrics steam ultrasonic mass flow transmitter
Table of Contents

Advertisement

Option Card Frequency Outputs
This type of output produces a frequency pulse that is proportional to the output measurement. Complete the following
steps to set up the frequency outputs of an option card installed in
1. Double-click on the desired Output (A, B, C or D).
Note: The set up of output A is used as an example. Identical procedures would be used to set up the other outputs.
2. Double-click on Off to disable Output A and return to step 1, or on Frequency to set up output A as a frequency
output.
For a 1-Channel meter, skip to step 4.
3. Double-click on the desired Channel option.See Table 28 on page 121 for a description of the channel options
available at the above prompt.
4. Double-click on the desired Measurement Name. (Table 27 on page 117 provides a description of the available
parameters.)
Note: The measurement units that appear in these prompts are those selected in the
this section.
5. Enter a flow rate value for the Zero (low) end of the frequency output range and click [Next Item].
6. Enter a flow rate value for the Full (high) end of the frequency output range and click [Next Item].
7. Enter a value between 1 and 10,000 for the Full Scale Frequency and click [Next Item].
After responding to the above prompt, the meter returns to step 1. Click [Exit Page]:
once to return to the Global I/O option:
twice to return to the Global PROGRAM option:
three times to return to the Site Edit Menu:
four times to exit the Site Edit Menu.
DigitalFlow™ XGS868i Programming Manual
Appendix C. Programming the XGS868i Using PanaView™
Slot 1
(see Figure 55 on page 142):
Global-System
menu earlier in
123