Chapter 1. Programming Site Data
1.9.2d
Analog Inputs
Refer to Figure 31 on page 80, and complete the following steps to set up the analog inputs of an option card installed
Slot 1
in
:
Accessing the Input
1. In the Keypad Program, scroll to PROG and press [Enter].
2. In the PROG menu, scroll to GLOBL and press [Enter].
3. In the Global PROGRAM menu, scroll to I/O and press [Enter].
4. Scroll to OPTN and press [Enter].
5. Scroll to Slot 1 and press [Enter].
6. Scroll to the desired Input and press [Enter].
Note: Input letters (A, B, etc.) correspond to input wiring terminal numbers from top to bottom (e.g. Input A
corresponds to pins 1,2 and 3; Input B corresponds to pins 4, 5 and 6; etc.).
Setting Up the Input
1. Enter a Label of up to eight characters for input and press [Enter].
2. Scroll to the desired input Measurement and press [Enter]. Do one of the following:
Off
If
was selected, go to Procedure Options below.
Pressure
Temperature
If
or
Special
If
was selected to set up the input as a live special input, proceed to the next step.
3. Use the arrow keys to enter a Name for the input and press [Enter].
4. Use the arrow keys to enter a Unit of measurement for the input and press [Enter].
5. Use the arrow keys to enter a value (a temperature value for special inputs) for the low end of the analog input
range and press [Enter].
6. Use the arrow keys to enter a value (a temperature value for special inputs) for the high end of the analog input
range and press [Enter].
Procedure Options
After completing the above steps, the XGS868i returns to the I/O window. Do one of the following:
To continue programming, refer to Appendix A, Menu Maps, to navigate to the desired menu.
To leave the Keypad Program, press [Escape] four times.