Descriptions of functions
10.3 PROFINET IO
10.3
PROFINET IO
10.3.1
Activating online mode: STARTER via PROFINET IO
Description
The following options are available for activating online mode via PROFINET IO:
● Online mode via IP
Preconditions
● STARTER with Version ≥ 4.1.5 (SINAMICS DCM is supported starting only from
● CBE20
STARTER via PROFINET IO (example)
Figure 10-18 STARTER via PROFINET (example)
Procedure for activating online mode with PROFINET
1. Set the IP address in Windows XP
2. Settings in STARTER
3. Enter the IP address and a name for the drive unit's PROFINET interface.
4. Select online mode in STARTER.
364
STARTER Version 4.1.5)
This involves assigning a fixed, free IP address to the PC/PG.
The PROFIBUS interface must be named so that STARTER can establish
communication.
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619
SINAMICS DCM DC Converter