The rated armature DC current for the unit must be adjusted by setting p50076[0] (in %) or
p50067 if:
Maximum armature current < 0.5 × rated armature DC current for the unit
The rated field DC current for the unit must be adapted by setting p50076[1] (in %) if:
Maximum field current < 0.5 × rated field DC current for the unit
Adapt to the actual unit supply voltage
p50078[0]
p50078[1]
Acquiring the motor data
The motor data can be taken from the motor rating plate.
Figure 8-4
p50100[d]
p50101[d]
p50102[d]
p50103[d]
p50114[d]
When you have finished entering the motor data, choose "Continue" underneath the final
parameter value and activate with <F5> (OK).
SINAMICS DCM DC Converter
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619
Rated input voltage for converter armature (in volts)
Rated input voltage for converter field (in volts)
Example of a rating plate
Rated armature current
Rated armature voltage
Rated excitation current
Minimum excitation current (optional)
Thermal time constant for motor
See the section titled "Thermal overload protection for the DC motor (I2t
monitoring of the motor)"