〈2〉Adjust the rated unit currents
NOTICE
The US rating must be set at p50067 for base drives (type 6RA80xx-2xxxx) manufactured
in North America.
The rated armature DC current for the unit must be adjusted by setting p50076[0] (in %) or
p50067 if:
Maximum armature current < 0.5 × rated armature DC current for the unit
The rated field DC current for the unit must be adapted by setting p50076[1] (in %) if:
Maximum field current < 0.5 × rated field DC current for the unit
〈3〉Adjust to the actual unit supply voltage
p50078[0]
p50078[1]
〈4〉Enter the motor data
The motor data, as specified on the motor rating plate, must be entered in the following
parameters (see also the sections titled
"Speed-dependent current limitation"
Figure 8-1
SINAMICS DCM DC Converter
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619
Rated input voltage for converter armature (in volts)
Rated input voltage for converter field (in volts)
Example of a rating plate
8.2 Commissioning using the BOP20 operator panel
"Thermal overload protection for the DC motor"
):
Commissioning
and