7.4.3.10

X542 relay outputs

Table 7- 35
X542 terminal strip
Terminal
1
2
3
4
5
6
DO: Digital output; NO: Normally open contact; NC: Normally closed contact; COM: Mid-
1)
position contact
depending on the parameters assigned and the supply voltage (P24) of the TM31
2)
SINAMICS DCM DC Converter
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619
Designation
1)
DO 0.NC
DO 0.COM
DO 0.NO
DO 1.NC
DO 1.COM
DO 1.NO
Technical specifications
Contact type: Two-way contact max. load current: 8 A
Max. switching voltage: 250 V
max. switching power at 250 V
max. switching power at 250 V
max. switching power at 30 V
Required minimum current: 100 mA
Output delay: ≤ 20 ms
2)
Overvoltage category: Class III to EN 60 664-1
Additional system components
7.4 Terminal Module TM31
, 30 V
AC
DC
: 2000 VA (cosϕ = 1)
AC
750 VA (cosϕ = 0.4)
AC:
: 240 W (resistive load)
DC
213