Siemens SINAMICS DCM Operating Instructions Manual page 56

Dc converter
Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Technical data
4.3 Unit data
Table 4- 25
Technical data for 3-ph. 400 V AC, 15 A to 90 A, 4Q units
Order number 6RA80 ..
Rated DC current
Rated armature input current 2)
Rated power
Power loss at rated DC current
(approx.)
Rated
field supply voltage 1)
Rated
field DC voltage 1)
Rated field DC current
Type of cooling
Dimensions (HxWxD)
Weight (approx.)
Rated DC voltage for single-phase
operation
Rated DC current for single-phase
operation
Table 4- 26
Technical data for 3-ph. 400 V AC, 125 A to 280 A, 4Q units
Order number 6RA80 ..
Rated DC current
Rated armature input current 2)
Rated power
Power loss at rated DC current
(approx.)
Rated
field supply voltage 1)
Rated
field DC voltage 1)
Rated field DC current
Type of cooling
Rated
fan supply voltage
Fan air flow
Fan noise level
Dimensions (HxWxD)
Weight (approx.)
54
..13-6DV62
A
15
A
12.5
kW
6.3
W
131
V
V
325
A
3
Self-ventilated
mm
385x268x221
kg
11
V
280
A
10.5
..31-6DV62
A
125
A
104
kW
52.5
W
409
V
V
325
A
10
Self-ventilated
V
-
m
/h
-
3
dBA
-
mm
385x268x252
kg
14
..18-6DV62
..25-6DV62
30
24.9
49.8
12.6
25.2
180
250
2-ph. 400 V AC (+15 % / – 20 %)
325
325
5
Self-ventilated
Self-ventilated
385x268x221
385x268x252
11
280
280
21.0
42.0
..75-6DV62
210
174
88.2
689
2-ph. 400 V AC (+15 % / – 20 %)
325
15
Forced ventilation
Fan with internal power
supply
300
70.3
385x268x252
15
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619
..28-6DV62
60
90
74.7
37.8
321
325
10
10
Self-ventilated
385x268x252
11
14
280
63.0
..78-6DV62
280
232
118
812
325
15
Forced ventilation
Fan with internal power
supply
300
70.3
385x268x252
15
SINAMICS DCM DC Converter

Advertisement

Table of Contents
loading

Table of Contents