Additional system components

Note
The components described here are used in several units in the SINAMICS family. The next
section may, therefore, contain references to manuals for these units.
The SINAMICS DC MASTER supports the following components from the SINAMICS drive
system:
CBE20
SMC30
TM15
TM31
In order to operate the SINAMICS DC MASTER with these components, it must be equipped
with (an) Advanced CUD(s); see the list of options in Chapter 2.
The Communication Board CBE20 can be ordered as an option for the SINAMICS DC
MASTER and is installed directly in the unit (in the OMI (Option Module Interface) slot of the
CUD).
The SMC30, TM15, and TM31 modules are installed separately and connected to the
SINAMICS DC MASTER via the DRIVE-CLiQ interface.
DRIVE-CLiQ interface
On the SINAMICS DC MASTER, up to 3 terminal modules TM15 / TM31 can be connected
to the DRIVE-CLiQ in any desired combination and in addition 1 Sensor Module Cabinet-
Mounted SMC30 can be connected.
The CUD features 2 DRIVE-CLiQ ports (X100, X101). Any combination of the modules can
be connected in series or in parallel. An SMC30 only possesses one DRIVE-CLiQ interface
and is, therefore, always the last module on the bus.
SINAMICS DCM DC Converter
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619
Communication Board
Sensor Module Cabinet-Mounted
Terminal Module
Terminal Module
7