Commissioning
8.2 Commissioning using the BOP20 operator panel
p50100[D]
p50101[D]
p50102[D]
p50104[D]
p50105[D]
p50106[D]
p50107[D]
p50108[D]
p50109[D]
p50114[D]
〈5〉Data for actual speed value acquisition
〈5.1〉Operation with analog tachometer
p50083[D] = 1 The actual speed value comes from the "Main actual value" (r52013)
p50741[D]
p2000
〈5.2〉Operation with incremental encoder
p50083[D] = 2 The actual speed value comes from an incremental encoder (r0061)
p0400[0]
p2000
226
Rated armature current (in amperes)
Rated armature voltage (in volts)
Rated excitation current (in amperes)
Speed n1 (in rpm)
Armature current I1 (in amperes)
Speed n2 (in rpm)
Armature current I2 (in amperes)
Maximum operating speed n3 (in rpm)
1 = Speed-dependent current limitation active
Motor thermal time constant (in seconds)
channel
(terminals XT.103, XT.104).
Tachometer voltage at maximum speed (– 270.00 to +270.00 V)
Remark:
The value set here determines the 100% speed for the closed-loop speed
control.
Speed in rpm for tachometer voltage set on p50741[0]
Comment 1:
Parameter p2000 is used to convert from a "physical speed" (rpm) into a
"relative speed" (%) and vice versa.
This conversion is required for:
 Speed setpoint input via the control panel in STARTER
 Speed setpoint input via the operating screen form at the AOP30
 Calculating the display values r020, r021, r060 and r063
Remark 2:
Parameter p2000 and parameters r020, r021, r060 and r063 are not data-set
dependent. This is the reason that the physical speed can only be displayed
correctly for one data set (DDS).
connected to terminal block X177.
Encoder type selection
Speed in rpm at 100% speed
Remark:
The value set here determines the 100% speed for the closed-loop speed
control.
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619