Monitoring The High Limit Temperature 'J.\\Tmax - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioners with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Parameter assignment
9.3 Description of parameters
H3.LEVL2 - threshold 2
Adjustment range:
Purpose:
Factory setting:
H4.LEVL3 - threshold 3
Adjustment range:
Purpose:
Factory setting:
9.3.3.9

Monitoring the high limit temperature 'J.\\TMAX'

J. TMAX - Monitoring the upper limit temperature
Requirement:
Possible settings:
Purpose:
Factory setting:
190
-40.0C ... 90.0C
-40.0F ... 194.0F
Use this sub-parameter to set the temperature for threshold 2.
The positioner triggers a message if the current temperature inside
the enclosure undershoots threshold 2. The process to activate and
display this message is described in the 'XDIAG' parameter.
-30.0C
-40.0C ... 90.0C
-40.0F ... 194.0F
Use this sub-parameter to set the temperature for threshold 3.
The positioner triggers a message if the current temperature inside
the enclosure undershoots threshold 3. The process to activate and
display this message is described in the 'XDIAG' parameter.
-40.0C
The '50.XDIAG' Activation of extended diagnostics (Page 170) pa‐
rameter is set to 'On1', 'On2' or 'On3'.
● OFF
● On
The current temperature inside the enclosure of the field device is
recorded by a sensor on the basic electronics. Use this parameter
to activate continuous monitoring of the high limit temperature inside
the enclosure. Monitoring is performed in three steps. To activate
monitoring, set the parameter to 'On'. Sub-parameters are dis‐
played. Appropriately set the sub-parameters.
The value is displayed in Diagnostic value '31.TMIN - Minimum tem‐
perature' / '32.TMAX - Maximum temperature' (Page 264). The po‐
sitioner triggers a message if the current value exceeds one of the
three thresholds.
OFF
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB