An input signal can be analyzed for specific frequencies and duty factors via the "FRQ"
frequency blocks. Two identical frequency analysis blocks are available, capable of detecting
frequencies of 1 Hz and 0.5 Hz with a duty factor of 20 %.
The detection criteria and the valid tolerances are described in detail in the following figure.
Input signal
Output signal
The output signal changes after 3 detected signal periods after the 4th edge
An input tolerance of (±) 40 ms is assumed.
Duty cycle: 20 % (17 to 23 %)
1 Hz frequency detection:
T = 1000 ms (±2 %)
t
= 200 ms
on
t
= 800 ms
off
Pulse/pulse ratio V = 25 %
0.5 Hz frequency detection:
T = 2000 ms (±2 %)
t
= 400 ms
on
t
= 1600 ms
off
Pulse/pulse ratio V = 25 %
Image 6-8
Frequency-based input signal detection
The outputs Q24 or Q26 become active when the analysis algorithm detects a frequency of
1 Hz with a 20 % duty factor in the input signal. The outputs Q25 or Q27 become active
when the analysis algorithm detects a frequency of 0.5 Hz with a 20 % duty factor in the
input signal.
The maximum response time at the output, i.e. the time after which the system can detect an
error or a deviation in the input signal frequency, corresponds to the period of the frequency
to be detected. Accordingly, a frequency of 1 Hz results in a maximum response time of 1 s
and a frequency of 0.5 Hz results in a maximum response time of 2 s.
6.2.43.8

On delay block

The "OnDELAY" block delays the input signal at the output Q28 by 2 s and at the output Q29
by 5 s.
92
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
System Manual, 06/2016, A2B00096162-AN