Mitsubishi L Series User Manual page 89

Analog-digital converter module
Hide thumbs Also See for L Series:
Table of Contents

Advertisement

The initial value of the shifting amount to conversion value is 0.
Item
Shifting amount to conversion value
If the digital output value exceeds the range of -32768 to 32767 as a result of shift addition, the digital output value is fixed to
the lower limit value (-32768) or the upper limit value (32767).
(3) Setting example
When the following settings are used for a channel with input range of -10 to 10V:
Ex.
• "Shifting amount to conversion value": 20000
The following figure and table show CH1 Digital output value (Un\G11) and CH1 Scaling value (digital operation
value) (Un\G54).
1) CH1 Digital output value
(Un\G11)
+
CH1 Shifting amount
to conversion value
(Un\G150)
2) CH1 Scaling value
(digital operation value)
(Un\G54)
Input voltage (V)
-10
-5
0
5
10
*1
Since the value exceeds the range of -32768 to 32767, it is fixed to 32767 (the upper limit value).
2) Scaling value
(digital operation value)
(after adjustment)
40000
32767
+20000
20000
0
-20000
-10
-5
0
CH1 Digital output value (Un\G11)
-20000
-10000
0
10000
20000
CHAPTER 8 FUNCTIONS
Setting range
-32768 to 32767
1) Digital output value
(before adjustment)
Analog input voltage (V)
5
10
CH1 Scaling value (digital
operation value) (Un\G54)
0
10000
20000
30000
32767
8
*1
87