Analog-digital converter module
Hide thumbs Also See for L Series:
Table of Contents

Advertisement

(35)CH
Logging points after trigger (Un\G1048 to Un\G1051)
When the logging function is used, set the data points recorded from hold trigger occurs until logging holds
(stops).
For details on the logging function, refer to the following.
• Logging function (
(a) Setting range
Setting range is 1 to 10000.
(b) Enabling the setting
Turn OFF → ON → OFF Operating condition setting request (Y9) to enable the setting.
(c) Default value
All channels are set to 5000.
● In the channel where a value out of the above range is set, an error occurs. Then, the error code is stored in Latest error
code (Un\G19), Error flag (XF) is turned to ON and logging cannot be performed.
● When CH
points after trigger (Un\G1048 to Un\G1051) is ignored.
(36)CH
Level trigger condition setting (Un\G1056 to Un\G1059)
When the level trigger is used with the logging function, set the occurrence condition of the hold trigger.
For details on the logging function, refer to the following.
• Logging function (
(a) Enabling the setting
Turn OFF → ON → OFF Operating condition setting request (Y9) to enable the setting.
(b) Default value
All channels are set to Disable (0).
● In the channel where a value other than the above setting values is set, an error occurs. Then, the error code is stored in
Latest error code (Un\G19), Error flag (XF) is turned to ON and logging cannot be performed.
● When CH
trigger condition setting (Un\G1056 to Un\G1059) is ignored.
192
Page 98, Section 8.14)
Logging enable/disable setting (Un\G1000 to Un\G1003) is set to Disable (1), the setting for CH
Page 98, Section 8.14)
Setting
Disable
Above
Below
Pass through
Logging enable/disable setting (Un\G1000 to Un\G1003) is set to Disable (1), the setting for CH
Logging
Setting value
0
1
2
3
Level