(3) Setting procedure
1.
Set "A/D conversion enable/disable setting" to "0: Enable".
Project window
2.
Set "Scaling enable/disable setting" to "0: Enable".
3.
Set values for "Scaling upper limit value" and "Scaling lower limit value".
Item
Scaling upper limit value
Scaling lower limit value
● Even if you set the scaling upper limit value and the scaling lower limit value in such a way that the change is larger than
the resolution, the resolution will not increase.
● Your scaling settings must meet the following condition:
Scaling upper limit value > Scaling lower limit value