Mitsubishi L Series User Manual page 223

Analog-digital converter module
Hide thumbs Also See for L Series:
Table of Contents

Advertisement

(1) CH
Scaling value (digital operation value) (Un\G54 to Un\G57)
When the digital clipping function, scaling function, shift function, or difference conversion function is not used, the
same value as the one in CH
(a) When the non-compatible version of A/D converter module is used
When the scaling function is not used, the value is not stored in CH
(Un\G54 to Un\G57).
(2) Maximum value/minimum value hold function
The scaling value (digital operation value) is stored in CH
and CH
Minimum value (Un\G31, Un\G33, Un\G35, Un\G37).
For details on the function, refer to the following.
• Maximum value/minimum value hold function (
(a) When the non-compatible version of A/D converter module is used
When the scaling function is not used, the digital output value is stored in CH
Un\G32, Un\G34, Un\G36) and CH
function is used, the scaling value (digital operation value) is stored in CH
Un\G34, Un\G36) and CH
(3) Input signal error detection function
The detection cycle is changed to the sampling cycle.
For details on the function, refer to the following.
• Input signal error detection function (
(a) When the non-compatible version of A/D converter module is used
The detection cycle is detected per sampling cycle or averaging process cycle depending on the specified A/D
conversion method.
(4) Warning output function (Process alarm)
The alarm output function monitors CH
output and does not monitor CH
For details on the function, refer to the following.
• Warning output function (Process alarm) (
(a) When the non-compatible version of A/D converter module is used
When the scaling function is not used, the alarm output function monitors CH
Un\G14) for alarm output. When the scaling function is used, the alarm output function monitors CH
value (digital operation value) (Un\G54 to Un\G57) for alarm output.
Digital output value (Un\G11 to Un\G14) is stored.
Page 68, Section 8.6)
Minimum value (Un\G31, Un\G33, Un\G35, Un\G37). When the scaling
Minimum value (Un\G31, Un\G33, Un\G35, Un\G37).
Page 69, Section 8.7)
Scaling value (digital operation value) (Un\G54 to Un\G57) for alarm
Digital output value (Un\G11 to Un\G14) for alarm output.
Page 77, Section 8.9)
Scaling value (digital operation value)
Maximum value (Un\G30, Un\G32, Un\G34, Un\G36)
Maximum value (Un\G30,
Maximum value (Un\G30, Un\G32,
Digital output value (Un\G11 to
APPENDICES
A
Scaling
221