Mitsubishi L Series User Manual page 68

Analog-digital converter module
Hide thumbs Also See for L Series:
Table of Contents

Advertisement

(b) Averaging processing
To select "1: Time Average" for "Averaging process setting":
Ex.
1.
Set "A/D conversion enable/disable setting" to "0: Enable".
Project window
2.
For "Averaging process setting", select "1: Time Average".
3.
For "Time Average/ CountAverage/Moving Average", enter the following:
Setting item
Time Average
Count Average
Moving Average
The following table shows the conversion cycle of each A/D conversion.
A/D conversion
method
Sampling processing
Time average
Count average
Moving average
*1
The value after the decimal point is rounded off.
66
[Intelligent Function Module]
Conversion speed
20 µs
80 µs, 1 ms
20 µs, 80 µs, 1 ms
20 µs, 80 µs, 1 ms
Conversion speed × Number of used channels
Time set in "Time Average/Count Average/Moving Average"
Conversion speed
Number of times set in "Time Average/Count Average/Moving Average" × Conversion speed ×
Number of used channels
Conversion speed × Number of used channels
module name
2 to 1500 ms
2 to 5000 ms
4 to 62500 times
2 to 1000 times
Conversion cycle
Number of used channels
[Parameter]
Setting range
*1
Conversion
Number of
speed
used channels